Tel. +44 (0) 1905 794 331 Email. info@nu-way.co.uk
This burner is suitable for use on natural gas and LPG (Towns gas and biogas on request) with-
• two stage high/low
• or modulating operation.
All N series burners are custom-built and designed for easy maintenance. This range is typically suited for high resistance, hot water and steam boilers.
Burner type | Gas Fired |
---|---|
Output | 388 – 983 |
Series | Gas > NGN Series |
Burner Type | NG35 | |
Capacity | kW | 388-983 |
Motor | V/ph/Hz | 380-420/3/50 |
kW | 1.1 | |
Start Current | A/each phase | 15 |
Run Current | A/each phase | 2.5 |
Cable size | mm2 | 1.0 |
Fuse | HRC (A) | 10 |
Control unit | LFL | |
Operation Options | 2 Stage / Mod | |
Flame monitoring | UV Cell | |
Air damper motor | • | |
Max inlet gas pressure | mbar | 300 |
Noise @ 1m | dBA | 87 |
Gross weight | kg | 75 |
Volume | m3 | 0.77 |
Key Features:
• Quick and easy installation
• Reliable and trouble free operation
• Industry standard components available
• Most components can be easily accessed allowing for easy maintenance.
Also available:
• Large gas train options
• Electronic Micro Modulating control
• Variable speed drive to reduce power consumption and noise levels.
All N series burners have been design in accordance with EN676 and EN267.
Necessary cookies are absolutely essential for the website to function properly. This category only includes cookies that ensures basic functionalities and security features of the website. These cookies do not store any personal information.
Any cookies that may not be particularly necessary for the website to function and is used specifically to collect user personal data via analytics, ads, other embedded contents are termed as non-necessary cookies. It is mandatory to procure user consent prior to running these cookies on your website.