The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW.

The PO Series burner is commonly used on large industrial steam and hot water boilers.

SKU: PO310 Category:
Additional Information
Burner type

Oil Fired

Output

6900 – 8300

Series

Oil > POL Series

Technical data
Output: 3900 - 8300 kW Output
 Model PO310/7.7310/8.0310/8.4310/8.8310/9.2
 Output (nett CV)MW6.97.27.67.98.3
 Fan SizekW15151518.518.5
 Pump Motor  (Distillate Fuel)kW3.03.03.04.04.0
 Pump Motor  (Residual Fuel)kW3.03.03.04.04.0
 Pre-heater  (Residual Fuel only)kW3636364848
 Electrical SupplyV/Hz400/50400/50400/50400/50400/50
 Oil inlet pressurepsi5 to 105 to 105 to 105 to 105 to 10
 Fuel pumpT3 / T4T3 / T4T3 / T4T3 / T4T3 / T4
 OperationFully ModulatingFully ModulatingFully ModulatingFully ModulatingFully Modulating
 Control UnitAutoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7Autoflame Mini Mk7
 Turndown up to 4:1up to 4:1up to 4:1up to 4:1up to 4:1
 Flame MonitorUV SensorUV SensorUV SensorUV SensorUV Sensor
 Flame tube lengthsmm430/610430/610430/610430/610430/610
 NoisedBA9696969696
 NOxmg/kWh200-280200-280200-280200-280200-280
 COmg/kWh<110<110<110<110<110

Key Features:

• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control
 

All P series burners are design and manufactured in accordance with EN746.
 