Quick find spares
Search

POL250 BURNER

Brands:NUWAY

The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW.

The PO Series burner is commonly used on large industrial steam and hot water boilers.

SKU: PO250 Category:
Burner type

Oil Fired

Output

4600 – 6600

Series

Oil > POL Series

Output: 4600 - 6600kW Output
 Model PO 250/5.1 250/5.5 250/6.0 250/6.2 250/6.6 250/7.0 250/7.3
 Output (nett CV) MW 4.6 5.4 5.4 5.6 5.9 6.3 6.6
 Fan Size kW 11 11 11 11 11 15 15
 Pump Motor  (Distillate Fuel) kW 3.0 3.0 3.0 3.0 3.0 3.0 3.0
 Pump Motor  (Residual Fuel) kW 1.5 1.5 1.5 3.0 3.0 3.0 3.0
 Pre-heater  (Residual Fuel only) kW 24 24 24 30 30 30 36
 Electrical Supply V/Hz 400/50 400/50 400/50 400/50 400/50 400/50 400/50
 Oil inlet pressure psi 5 to 10 5 to 10 5 to 10 5 to 10 5 to 10 5 to 10 5 to 10
 Fuel pump   KSA1600 / T3 KSA1600 / T3 KSA1600 / T3 KSA1600 / T3 KSA1600 / T3 KSA1600 / T3 KSA1600 / T3
 Operation   Fully Modulating Fully Modulating Fully Modulating Fully Modulating Fully Modulating Fully Modulating Fully Modulating
 Control Unit   Autoflame Mini Mk7 Autoflame Mini Mk7 Autoflame Mini Mk7 Autoflame Mini Mk7 Autoflame Mini Mk7 Autoflame Mini Mk7 Autoflame Mini Mk7
 Turndown   up to 4:1 up to 4:1 up to 4:1 up to 4:1 up to 4:1 up to 4:1 up to 4:1
 Flame Monitor   UV Sensor UV Sensor UV Sensor UV Sensor UV Sensor UV Sensor UV Sensor
 Flame tube lengths mm 430/610 430/610 430/610 430/610 430/610 430/610 430/610
 Noise dBA 93 93 93 93 93 93 93
 NOx mg/kWh 200-280 200-280 200-280 200-280 200-280 200-280 200-280
 CO mg/kWh <110 <110 <110 <110 <110 <110 <110

Key Features:

• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control

All P series burners are design and manufactured in accordance with EN267 and EN676.

We help you to unlock & unleash the power within your Business…

×